Washington's eyewash rule sets two tests for a station a count crew can use: it must take no more than ten seconds to reach, and it must deliver at least 20 gallons (75 liters) each minute for fifteen minutes or more. Both figures come from WAC 296-800-15030, the state's rule for emergency washing facilities, so you can check your station against the rule's own wording.
Tidy takeaways
- Place the station so it takes no more than ten seconds to reach from the work area ( WAC 296-800-15030).
- Confirm the station delivers at least 20 gallons (75 liters) each minute ( WAC 296-800-15030).
- Plan for a flush that runs fifteen minutes or more, not a quick rinse ( WAC 296-800-15030).
- Match the chemicals your crew handles against the rule's list before you decide what to install ( WAC 296-800-15030).
The answer on reach and flow
The reach test is about time, not distance. Washington's rule says the station must be located so that it takes no more than ten seconds to reach ( WAC 296-800-15030). That wording gives you something you can test on a walk-through. Stand where the count crew works, start a stopwatch, and walk to the station without running. If the clock passes ten seconds, the station fails the reach test, even if it sits in the same room. Count the path, not the floor plan. Doors that swing into the walkway, carts parked in the aisle, and a staircase all add seconds. A station that looks close on paper but is blocked in practice does not meet the rule.
The flow test is about a full drench. The same rule says the station must deliver water to cascade over the user's entire body at a minimum rate of 20 gallons (75 liters) each minute for fifteen minutes or more ( WAC 296-800-15030). The rule lists reach and flow as separate properties, marked (a) and (b), so a station has to satisfy both. Each part of the flow sentence sets a floor. "Minimum rate" means the station cannot run slower than 20 gallons each minute and still count. "Fifteen minutes or more" means a short rinse is not enough; the water has to keep running for that long. "Entire body" tells you the spray pattern matters as much as the volume. A small bottle or a single faucet that splashes the face would not match the cascade wording.
Read together, the two tests describe one station a person can reach in ten seconds and stand under for at least fifteen minutes. Neither test replaces the other. A station that is close but delivers only a trickle fails, and a powerful shower across the building fails too.
Reach and flow compared side by side
Reach and flow are two separate tests, and the table below sets them against each other on the same measures so you can check each one.
| Measure | Reach | Flow |
|---|---|---|
| What the test covers | Travel time to the station | Water delivered at the station |
| Figure set by the rule | No more than ten seconds ( WAC 296-800-15030) | At least 20 gallons (75 liters) each minute ( WAC 296-800-15030) |
| Wording that applies | Located so that it takes no more than ten seconds to reach ( WAC 296-800-15030) | Cascades over the user's entire body for fifteen minutes or more ( WAC 296-800-15030) |
| How to check it | Time the walk with a stopwatch | Run the station and time it while you watch the spray |
Reading across the rows, the reach figure is a ceiling and the flow figure is a floor. The reach figure sets a maximum of ten seconds. The flow figure sets a minimum of 20 gallons (75 liters) each minute, and that must hold for fifteen minutes or more ( WAC 296-800-15030). Because the two tests are measured differently, a station can pass one and fail the other. A crew that sees a sink close by should not assume it can deliver the flow the rule requires.
Which chemicals need emergency washing facilities
The rule contains a lead-in sentence that reads "Chemicals that require emergency washing facilities:" ( WAC 296-800-15030). That sentence introduces a list. The rule ties the requirement for emergency washing facilities to the chemicals named in that list, so the list is the trigger. Your first job is not to buy a station. It is to match the chemicals in your building against the list.
Start with what is on your shelves. Count crews often carry cleaners, lubricants, and other products they do not think of as hazardous, so walk the storage area and read the labels. Write down each product name, then compare it against the chemicals named in the rule. Use the exact names from the list. A similar name is not a match until you have checked it against the wording. If a product matches, the station that serves that work area must meet the reach and flow tests described above. If nothing on your shelves matches, you can show the list and your comparison to anyone who asks.
Keep the comparison current. Chemicals change when suppliers change formulas or when a crew brings in a new product for a count, so repeat the match whenever you buy new stock. Also note which work areas the matching chemicals reach. A station in the front office does not help a crew working in a back room with a chemical on the list, so apply the reach test to the work area, not just to the building.
Why 20 gallons each minute for fifteen minutes is the floor
The flow requirement is written as a minimum in two places: the rate and the duration. The rule asks for water delivered at a minimum rate of 20 gallons (75 liters) each minute for fifteen minutes or more ( WAC 296-800-15030). Both halves of that phrase are floors. A station that runs below 20 gallons each minute misses the rule, and so does one that stops before fifteen minutes have passed.
| Element | Quoted minimum | Source |
|---|---|---|
| Flow rate | 20 gallons (75 liters) each minute ( WAC 296-800-15030) | Washington rule (b) |
| Run time | Fifteen minutes or more ( WAC 296-800-15030) | Washington rule (b) |
| Spray pattern | Water cascades over the user's entire body ( WAC 296-800-15030) | Washington rule (b) |
The rule gives both gallons and liters, so you can check a spec sheet in either unit. Do not round across units. A product labeled in liters should be compared against 75 liters each minute, not 20, and a product labeled in gallons should be compared against 20.
Check the unit on the rating, then time the run with a clock rather than trusting the label. Because the rule says "for fifteen minutes or more," a station that reaches its full rate only briefly fails the duration floor even if the rate is correct. Treat the spec sheet as a claim to test, not a finished answer.
Worked example: what one fifteen-minute flush asks of the station
Take the two floors from the rule and see what they ask of a station in practice. The rule sets a minimum flow of 20 gallons each minute and a minimum run time of fifteen minutes ( WAC 296-800-15030). It also gives the same minimum rate as 75 liters each minute ( WAC 296-800-15030).
Put the two floors together and a single flush at the minimum has to hold the full rate for the full time. The station cannot deliver 20 gallons each minute for the first minute and then taper off. Read in liters, the same requirement is 75 liters each minute held for fifteen minutes. Either way, the test is sustained delivery, not a strong opening burst.
The rule gives a rate and a duration, not a total volume for one flush, so the quote does not set a volume figure. If you need a planning number, take it from your station's rated flow and the run time you have timed on site, and keep the units the same from start to finish. Do not mix a gallon rate with a liter-based rate, and do not compare a liter-labeled product against the gallon figure.
The ten-second reach limit does not change the flow requirement. It sets how fast a worker must reach the water once an exposure happens. Walk the route in your own time. If the walk takes longer than ten seconds, the station fails the rule even if it can deliver the full flow for fifteen minutes.
How we worked out: we took the minimum flow of 20 gallons (75 liters) each minute and the fifteen-minute minimum run time, both from WAC 296-800-15030, and read them as a single sustained requirement. The quote gives no year, so none is stated here.
Heat emergency plans and Oregon's rule
Eyewash is not the only emergency a count crew may face. Oregon's administrative rules also address heat. According to the Oregon Secretary of State's rule page, the employer's Emergency Medical Plan must address employee exposure to excessive heat, in accordance with OAR 437-002-0161(4).
That sentence does three things. It names the employer as the party responsible. It names the document, the Emergency Medical Plan. And it says the plan must cover employee exposure to excessive heat. The quote does not describe what the plan must contain beyond that, so do not fill in details from memory. Read the cross-referenced rule, OAR 437-002-0161(4), before you write heat steps into your plan.
Keep the heat section separate from your eyewash checklist. The eyewash figures come from Washington's rule, and the heat requirement comes from Oregon's rule. A crew in one state cannot assume the other state's wording applies to it. If you operate in more than one state, list each state's requirement under its own heading so a manager can tell each rule apart.
Also consider where the two topics overlap in practice. A crew that is working in heat may need to reach the eyewash station, the first-aid kit, and a way to contact help without delay. Walk those routes together during your check. The reach test in Washington's rule is about time, so a route that is clear for an eyewash emergency is also easier to use in a heat emergency.
First aid and recordable injuries
Once a worker is treated, the next question is whether the case must be recorded. OSHA's heat standards page explains the recordkeeping rule in general terms: "The Recordkeeping regulation (29 CFR 1904) requires employers to record certain work-related injuries and illnesses" ( OSHA heat standards page).
The same page separates first aid from other care. It says that "if a worker needs 'first aid,' as defined in 29 CFR 1904.7(b)(5), the employer is not required to record the case" ( OSHA heat standards page). It also points to the same section for the difference between medical treatment and first aid: "Refer to 29 CFR 1904.7(b)(5) for an explanation of the difference between medical treatment and first aid" ( OSHA heat standards page). The page points readers to 29 CFR 1904.7(b)(5) for the first-aid definition, so check that section before you decide how to classify a case.
| Situation | Recording rule on OSHA's page |
|---|---|
| Worker needs first aid as defined in 29 CFR 1904.7(b)(5) | Employer is not required to record the case ( OSHA heat standards page) |
| Worker has days away from work | Case will need to be recorded ( OSHA heat standards page) |
| Worker has restricted work activity or job transfer | Case will need to be recorded ( OSHA heat standards page) |
| Worker receives medical treatment beyond first aid | Case will need to be recorded ( OSHA heat standards page) |
The table shows that the line falls between first aid and everything else. A rinse at the eyewash station may be first aid, but a visit to a clinic is a different question, and the page says to refer to the definition rather than guess.
Which one should you pick?
Owners and managers often ask whether to treat an incident as first aid or to record it. The quotes give you a clear decision path, even though they do not make the call for you. Start by asking what care the worker received. If the care was first aid as defined in 29 CFR 1904.7(b)(5), the page says the employer is not required to record the case. If the worker had days away, restricted work or job transfer, or medical treatment beyond first aid, the page says the case will generally need to be recorded.
Pick the option that matches the facts, not the one that feels easier. Choosing first aid because the worker went back to the floor after a rinse is a mistake if the worker later missed a shift or was moved to lighter duty. Those later events can change the case.
If you are unsure which category fits, use the definition as your reference point. The OSHA page points readers to 29 CFR 1904.7(b)(5) for the difference between medical treatment and first aid, so that section is the place to settle a close call. Write down the facts you relied on, so the decision can be reviewed later.
Steps to check your station against the rules
Use this sequence during a walk-through. It starts with the Washington eyewash tests and then moves to the recording question.
- Confirm which chemicals in your work areas appear on the list in Washington's rule, and note which stations serve those areas.
- Time the walk from each work area to the station. The rule's wording is "no more than ten seconds to reach" ( Washington rule), so a slow route fails even if the distance looks short.
- Run the station and check the flow. Confirm it delivers water to cascade over the user's entire body at a minimum rate of 20 gallons (75 liters) each minute, and time the run for fifteen minutes or more.
- Record the results with the date, the name of the person who checked, and any blockages you found.
- When an injury happens, decide whether the care was first aid using the definition in 29 CFR 1904.7(b)(5). Check the OSHA page for the recording rule before you close the case.
Repeat the checklist whenever you change chemicals, move shelves, or add a work area. A station that passed last year may fail after a rack is moved into the aisle.
Who this advice does not apply to
This post covers Washington's eyewash rule, Oregon's heat-emergency rule, and the OSHA recordkeeping rule as the quotes describe them. It does not cover every employer or every workplace. If you work outside Washington, the eyewash figures in this post are not a substitute for your own state's rule. Check the rules that apply where you operate.
The Oregon heat quote applies to an employer's Emergency Medical Plan under Oregon's rules. The quoted Oregon text covers an Emergency Medical Plan's heat provision and does not address eyewash stations, and it does not apply to employers in other states unless their own rules say the same thing. Treat it as a separate topic from the eyewash tests.
The recordkeeping quotes describe what the OSHA page says about recording work-related injuries and illnesses. The page does not say every workplace must keep the same records in the same way, and it does not replace the full regulation. For a close call, read 29 CFR 1904 and its definitions directly, or ask the person responsible for your safety program to review the case.
Related guides: California high-heat rules for count day: 5 duties · Pay for a short count-day call-in: 3 state pay checks · Count-day overtime: 40-hour and 8-hour triggers to check.
Reader questions answered
Does the ten-second rule mean the station must be within ten seconds of distance? The rule says the station must be located so that it takes no more than ten seconds to reach ( Washington rule). It measures time, so walk the route and time it.
Is a station that delivers less than 20 gallons each minute acceptable? The rule sets a minimum of 20 gallons (75 liters) each minute ( Washington rule). A station that delivers less does not meet that minimum.
How long must the water run? The rule says fifteen minutes or more ( Washington rule). A short rinse does not meet the duration in the rule.
Do I need an eyewash station for every chemical? The rule ties emergency washing facilities to the chemicals named in its list, which begins with "Chemicals that require emergency washing facilities" ( Washington rule). Compare your products against that list before you decide.
If a worker gets first aid, do I have to record it? The OSHA page says that if a worker needs first aid as defined in 29 CFR 1904.7(b)(5), the employer is not required to record the case ( OSHA heat standards page).
What makes a case recordable? The page says that if a worker has days away from work, restricted work activity or job transfer, or medical treatment beyond first aid, the case will generally need to be recorded ( OSHA heat standards page).
Where do I find the difference between first aid and medical treatment? The OSHA page refers readers to 29 CFR 1904.7(b)(5) for that explanation ( OSHA heat standards page).
Does Oregon's heat rule set eyewash requirements? The quoted Oregon text covers an Emergency Medical Plan addressing employee exposure to excessive heat, in accordance with OAR 437-002-0161(4) ( Oregon rule). Read that rule directly for its requirements.
Questions readers ask
Does Oregon's rule require heat planning in an emergency plan?
Yes. According to the Oregon rule, the employer's Emergency Medical Plan must address employee exposure to excessive heat, in accordance with OAR 437-002-0161(4). The quote names the employer as the responsible party and the Emergency Medical Plan as the document that must cover heat. For what that plan has to contain, read the cross-referenced rule.
Does the Washington rule say how the water must spray?
Yes. The Washington rule says the station must deliver water to cascade over the user's entire body at a minimum rate of 20 gallons (75 liters) each minute for fifteen minutes or more. Because the wording covers the entire body, the spray pattern is part of the requirement, along with the volume of water.
Where does the Washington rule say an eyewash station must be placed?
The Washington rule says the station must be located so that it takes no more than ten seconds to reach. The limit is expressed in time rather than as a fixed distance, so the walk a worker actually takes from the work area is what the rule measures. A station can look close on a floor plan and still fail if the route is slow, so time the walk to confirm it.
Does the Washington rule say which chemicals need emergency washing facilities?
The Washington rule introduces a list with the lead-in "Chemicals that require emergency washing facilities:". That wording ties the requirement for these facilities to the chemicals named in the list. The quoted line does not name any chemicals, so open the full rule to compare the list with the products in your building.
Where is first aid defined for OSHA recordkeeping?
The OSHA heat standards page says that if a worker needs "first aid," as defined in 29 CFR 1904.7(b)(5), the employer is not required to record the case. That section number is the reference point for the definition. Check it before you apply this exception to a specific injury, so you are working from the defined term rather than your own sense of what counts as first aid.
Which federal regulation governs recording work-related injuries and illnesses?
The OSHA heat standards page says the Recordkeeping regulation (29 CFR 1904) requires employers to record certain work-related injuries and illnesses. The quoted sentence refers to "certain" cases without listing them, so the regulation itself is the place to check which cases apply to your situation.
How do I classify care that might be medical treatment or first aid?
The OSHA heat standards page directs readers to 29 CFR 1904.7(b)(5) for an explanation of the difference between medical treatment and first aid. The page gives that reference but not the explanation itself, so open the referenced section before you classify a case.